作者
Hengwei Lin, Chengxi Liu, Josep M Guerrero, Juan C Vásquez
发表日期
2015/11/9
研讨会论文
IECON 2015-41st Annual Conference of the IEEE Industrial Electronics Society
页码范围
000731-000736
出版商
IEEE
简介
Owing to the increasing penetration of distributed generation, there are some challenges for the conventional protection in distribution system. Bidirectional power flow and variable fault current because of the various operation modes may lead to the selectivity and sensitivity of the overcurrent protection decreased. This paper adopts distance protection for one mid-voltage level microgrid in Aalborg, Denmark. Different operation modes of the network are analyzed and tested in the paper. The simulation results show that the variations of the fault currents seen by the forward relays are much larger than the backward relays. Meanwhile, the fault currents change little with the randomness of renewable energy except the intermittence. Finally, it shows that the designed distance protection has satisfactory performance to clear the various faults.
引用总数
2016201720182019202020212022202320243845814271
学术搜索中的文章
H Lin, C Liu, JM Guerrero, JC Vásquez - IECON 2015-41st Annual Conference of the IEEE …, 2015