作者
Raziyeh Mosayebi, Hamid Sheikhzadeh, Mohammad Sadegh Golsorkhi, Maryam Sadat Akhavan Hejazi, Gevorg B Gharehpetian
发表日期
2014/4/26
期刊
Electric Power Components and Systems
卷号
42
期号
6
页码范围
605-611
出版商
Taylor & Francis
简介
In this article, a new bi-static method for the detection and determination of magnitude and location of winding radial deformation in power transformers has been proposed. In this method, which is based on confocal microwave imaging, a ultra-wideband transceiver is utilized to emit a short pulse toward the transformer winding and determine its reflection at several points along a linear path. The measured signals are then processed to obtain a 2D image of the winding. The effectiveness of this algorithm for radial deformation is demonstrated through four different experiments. The resultant image provides satisfactory information of the magnitude and position of the radial deformation in transformer.
引用总数
20162017201820192020202120222023202411123211
学术搜索中的文章