作者
Angan Sengupta
发表日期
2019/9/1
期刊
Fire technology
卷号
55
页码范围
1771-1799
出版商
Springer US
简介
Fire hazard is one of the main risks associated to fuel storage tanks in petroleum and in the petrochemical industries. Such a hazard includes pool fires in the storage tanks or in the bunds, fire propagation from the source tank to target tanks both in absence and in presence of wind, and also the cascading/domino effect due to confined and unconfined vapour cloud explosion and or BLEVE associated with the source tank. In the present work, a radiation shield of flowing water has been introduced at a distance from the source fuel storage tank to prevent the domino effect originating from this source tank, under fire, to the target fuel storage tanks in a tank farm. A simple one dimensional model has been developed from the steady state energy balance to simulate the safe distances (i.e. rim–rim distance) between fuel storage tanks containing class-I fuel (e.g. gasoline), both in presence and absence of a water …
引用总数
2020202120222023202422311