a simple but yet effective passive heat and mass recovery schemes. It substantially improves
the adsorption chiller COP by as much as 30% over a broad range of cycle time with a wide
heat source, coolant and chilled water temperatures. Two schemes have been considered
here: Firstly, only the mass recovery is achieved by pressure equalization between the
concomitantly cooled adsorber and heated desorber, exploiting the intrinsic vapor-uptake …