GIS 绝缘子表面固定金属颗粒沿面局部放电发展的现象及特征

齐波, 李成榕, 郝震, 耿弼博, 徐党国… - 中国电机工程 …, 2011 - epjournal.csee.org.cn
为研究气体绝缘全封闭式组合电器(gas insulated switchgear, GIS) 设备中绝缘子表面固定金属
颗粒沿面局部放电发展的现象及其特征, 搭建了一套220 kV GIS 设备沿面放电缺陷发展实验 …

Surface discharge initiated by immobilized metallic particles attached to gas insulated substation insulators: process and features

B Qi, CR Li, Z Hao, BB Geng, DG Xu… - … on Dielectrics and …, 2011 - ieeexplore.ieee.org
In order to study the developing process of surface discharges initiated by immobilized
metallic particles attached to Gas Insulated Substation (GIS) insulators under gradually …

Dynamics of metallic particle contaminants in GIS with dielectric-coated electrodes

MM Morcos, S Zhang, KD Srivastava… - IEEE Transactions on …, 2000 - ieeexplore.ieee.org
Electrical insulation performance of compressed gas insulated switchgear (GIS) and gas
insulated transmission line (GITL) systems is adversely affected by metallic particle …

Partial discharge initiated by free moving metallic particles on GIS insulator surface: severity diagnosis and assessment

B Qi, C Li, Z Xing, Z Wei - IEEE Transactions on Dielectrics and …, 2014 - ieeexplore.ieee.org
Free moving metallic particles are one of the most common defects leading to insulation
failures in gas insulated substation (GIS) equipment. The present research is designed to …

[HTML][HTML] Suppression of Metal Particles by Coating for a±550 kV DC GIS

H Luo, D Gong, S Li, Z Zhan, N Di, D Dolkun, X Fan… - Energies, 2024 - mdpi.com
Coating the inner surface of grounded enclosures has been used to inhibit metal particle
motion inside AC GIS for many years. However, for DC GIS, only fundamental research has …

Investigation of the circuit breaker reignition overvoltages caused by no‐load transformer switching surges

M Popov, L Van Der Sluis… - European transactions on …, 2001 - Wiley Online Library
When an unloaded transformer or motor is switched under certain conditions, the circuit
breaker can be exposed to a re‐strike effect that leads to voltage escalation. The effect of …

Movement of particles in compressed SF/sub 6/GIS with dielectric coated enclosure

KS Prakash, KD Srivastava… - IEEE transactions on …, 1997 - ieeexplore.ieee.org
In compressed GIS (gas insulated switchgear), the control of wire particle contamination by
dielectric coating of enclosure is demonstrated in this paper. Assuming that a particle …

Electric field effect on metallic particle contamination in a common enclosure gas insulated busduct

GVN Kumar, J Amarnath, BP Singh… - IEEE Transactions on …, 2007 - ieeexplore.ieee.org
Sulphur hexaflouride (SF 6) is generally found to be very sensitive to field perturbations such
as those caused by conductor surface imperfections and by conducting particle …

Charging and behavior of a spherically conducting particle on a dielectrically coated electrode in the presence of electrical gradient force in atmospheric air

K Sakai, DL Abella, J Suehiro… - IEEE transactions on …, 2002 - ieeexplore.ieee.org
This paper discusses the charging and behavior of a spherically conducting particle on a
dielectrically coated electrode in non-uniform dc and ac electric fields between non-parallel …

Severity diagnosis and assessment of the partial discharge provoked by high-voltage electrode protrusion on GIS insulator surface

B Qi, C Li, B Geng, Z Hao - IEEE transactions on power …, 2011 - ieeexplore.ieee.org
High-voltage electrode protrusion is one of the major causes of insulation failure in gas-
insulated substation (GIS) equipment. The present research is designed to diagnose and …